DOWNLOAD

LB3980J

AC Load Bank

Regular AC load bank testing of generators provides an essential health check service to prevent diesel engine failure due to wet stacking. Wet stacking occurs due to under loading of the genset which results in wet un-burned fuel building up in the engine. PITE offers the AC load bank which could meet your demands.

DOWNLOAD
  • High rate testing for voltage, current and transient voltage waveform for generator and UPS units
  • Big TFT touch screen, easy operation and vivid display of testing data and waveform
  • Power continuously adjustable from 0 to 40kVA with current from 0 to 333A
  • Discharge time customized as 0-99 hours with resolution of 1 minute
  • Can set different current, end-up time, discharge power and voltage threshold (upper or lower limit)
  • Has emergency stop button
  • Auto stop discharge when three phase voltage is over high
  • Auto stop discharge when three phase voltage is over low.
  • Has over current short circuit protection
  • Warning and auto stop upon any fans failure
  • Can have two units working in parallel for higher output power

Product Specification (40KW, Single Phase):

Column 1 Column 2
Voltage Test: Test range: 120VAC, 0-40kVA, single phase
Accuracy: ±0.5%
Resolution: 0.1V
Current Test: Test range: AC 0~333A
Accuracy: ±1%
Resolution: 0.1A
Working power: 110V±10% 60Hz, 220V±10% 50Hz
Load input voltage: 120VAC, single phase
Cooling: Force air cooling
Communication: USB
Display: TFT touch screen, 320*240 pixel
Dimension& weight (main body): 740*400*740 (mm), 43kg